In Polish coal mining, medium voltage power distribution networks operate with an insulated neutral point. Zero-sequence current transformers are the basic sensors that generate input signals for earth-fault protection relays. In the literature, the problem of frequency response analysis of various types of current transformers has been examined many times, e.g. [1] [2], but not for zero-sequence current transformers so far. As part of the work, two types of zero-sequence current transformers in the range from 0.1 Hz to 100 kHz were tested. Both the change of the current ratio and the angular shift between the transformer secondary current and the total primary current were analyzed.

Przejdź do artykułu

Autorzy i Afiliacje

Krzysztof Kuliński
Adam Heyduk